CT-2228 - 8DO DC Source. Module kỹ thuật số ngõ ra 8 kênh 24VDC Source của Odot
CT-2228 Module kỹ thuật số ngõ ra 8 kênh 24VDC Source của Odot
Module features
◆ the module supports 8-channel digital output, output high level effective, and output voltage 24V
◆ the module could drive field equipment (relay, solenoid valve, etc.)
◆ the module internal bus and field output are isolated by optocoupler
◆ the module carries with 8 digital output channel LED indicator
◆ the module has the functions of thermal shutdown and overcurrent protection
◆ the module supports short circuit protection and overload protection
Technical Parameters
General Parameters |
|
Power Consumption |
Max.51mA@5.0VDC |
Isolation |
I/O to internal bus: opto-couple isolation (3KVrms) |
Field Power |
Nominal:24VDC, Range: 19.2~28.8VDC |
Wiring |
Max.: AWG 18 Min.: AWG 24 |
Installation |
35mm DIN-Rail |
Size |
115*14*75mm |
Weight |
65g |
Environment Specification |
|
Operating Temperature of Vertical Installation |
-35℃~70℃ |
Operating Temperature of Horizontal Installation |
-35℃~60℃ |
Relative Humidity |
5~ 95%RH (No Condensation) |
Storage Temperature |
-40℃~85℃ |
Storage Humidity |
5~ 95%RH (No Condensation) |
Manufacturing Test Temperature |
-40℃~75℃ |
Ingress Protection Rating |
IP20 |
Vibration Resistance |
Comply with IEC 61131-2 and EC 60068-2-6 |
Impact resistance |
Comply with IEC 61131-2 and IEC 60068-2-27 |
EMC Performance |
Comply with IEC 61131-2 and IEC 61000-4 |
Output Parameters |
|
Channel Number |
8 Channels |
LED Indicator |
8 Channels output LED Indicator |
Rated Current |
Typical value:500mA |
Leak Current |
Max. value:100uA |
Output Impedance |
<280mΩ |
Output Delay |
OFF to ON:Max.100us ON to OFF:Max.150us |
Protection Function |
Over temperature turn-off: typical 135℃ Overcurrent protection: typical value 1.1A |
Load type |
GENERAL USE LOADS, PILOT DUTY LOADS |