Module features

◆ the module supports 8-channel digital output, output high level effective, and output voltage 24V

◆ the module could drive field equipment (relay, solenoid valve, etc.)

◆ the module internal bus and field output are isolated by optocoupler

◆ the module carries with 8 digital output channel LED indicator

◆ the module has the functions of thermal shutdown and overcurrent protection

◆ the module supports short circuit protection and overload protection

Technical Parameters

General Parameters

Power Consumption

Max.51mA@5.0VDC

Isolation

I/O to internal bus: opto-couple isolation (3KVrms)

Field Power

Nominal:24VDC, Range: 19.2~28.8VDC

Wiring

Max.: AWG 18

Min.: AWG 24

Installation

35mm DIN-Rail

Size

115*14*75mm

Weight

65g

Environment Specification

Operating Temperature of Vertical Installation

-35℃~70℃

Operating Temperature of Horizontal Installation

-35℃~60℃

Relative Humidity

5~ 95%RH (No Condensation)

Storage Temperature

-40℃~85℃

Storage Humidity

5~ 95%RH (No Condensation)

Manufacturing Test Temperature

-40℃~75℃

Ingress Protection Rating

IP20

Vibration Resistance

Comply with IEC 61131-2 and EC 60068-2-6

Impact resistance

Comply with IEC 61131-2 and IEC 60068-2-27

EMC Performance

Comply with IEC 61131-2 and IEC 61000-4

Output Parameters

Channel Number

8 Channels

LED Indicator

8 Channels output LED Indicator

Rated Current

Typical value:500mA

Leak Current

Max. value:100uA

Output Impedance

<280mΩ

Output Delay

OFF to ON:Max.100us

ON to OFF:Max.150us

Protection Function

Over temperature turn-off: typical 135℃

Overcurrent protection: typical value 1.1A

Load type

GENERAL USE LOADS, PILOT DUTY LOADS