Flame Safeguard Primary Control RA890F

+84 828 600 900 Email: info@tblcorp.vn L17-11, Tầng 17, Toà nhà Vincom Center, 72 lê Thánh Tôn, Phường Bến Nghé, Quận 1, TP HCM
Tiếng Việt Tiếng Anh

Flame Safeguard Primary Control RA890F

The RA890F Protectorelay™ Primary Control is a nonprogramming, amplifying relay that provides solid state
electronic flame safeguard protection for industrial and commercial gas, oil, or combination gas-oil burners.
  • Thông tin sản phẩm
  • Tập tin
Flame Safeguard Primary Control RA890F
  • Employs rectification principle of electronic flame detection using a flame rod, rectifying photocell, or C7012A,C Ultraviolet Flame Detector.
  • Clipping pilot link jumper wire permits use with standing pilots
  • Can directly replace RA890E and mount on same Q270A Subbase
  • Solid state circuitry eliminates vacuum tube replacement and increases resistance to vibration. Power application not required during Off cycle; no tube to warm up before starting.
  • Push-to-reset safety switch in dust-resistant enclosure
  • Built-in protection against ignition crossover in flame rod systems
  • Does not start if flame-simulating failure occurs in flame detector circuit
  • Automatic safety shutdown if flame fails on start, or if flame not re-established after flame failure
  • Flame signal current is directly measurable at test jack
  • Line or 24 volt, automatic or manual controller can be used. (Manual controller must open circuit on either power or flame failure.)
  • Captive mounting screws allow easy mounting and removal. Thermoplastic mounting base
  • Optional alarm circuit indicates safety shutdown.
  • 0
  • Liên hệ
  • 828
Sản phẩm cùng loại
Zalo
Hotline